6000VA / 6kVA / 5400W on-line double-conversion 4U rack/tower UPS, Sine Wave
Included maintenance bypass switch enables live replacement of UPS with zero downtime
Extended runtime options, Interactive LCD interface, Economy-mode option, 0.9 power factor
USB, RS232 & EPO ports; Slot for network management card options
Hardwire 200-240V 50/60Hz (3 wire) input; Hardwire (3 wire) output; Configurable for 200/208/220/230/240V 50/60Hz output
2-year limited warranty

Overview
Featuring true on-line operation with pure sine wave output, zero transfer time to battery and complete UPS replacement capability with no downtime, the SU6000RT4UHVHW provides the highest level of protection available for mission-critical equipment from power outages, voltage fluctuations and transient surges. It converts incoming AC power to DC, and re-converts it back to filtered AC output with a pure sine wave, isolating connected components from all power problems in high-voltage environments. The SU6000RT4UHVHW has a 6kVA/5400W capacity and hardwire output.

With its detachable PDU with bypass switch, the SU6000RT4UHVHW is easily hot-swappable by a user of any skill set—no need for lengthy and expensive service calls, and no downtime if a repair or battery replacement is needed. In bypass mode, the PDU passes power to equipment without the use of the power and battery modules, allowing them to be removed while keeping your application in operation.

UPS battery backup keeps connected equipment operational through short power failures, and provides time to save data and perform an orderly system shutdown in case of a prolonged blackout. The SU6000RT4UHVHW’s runtime can be expanded with optional external battery packs.

The SU6000RT4UHVHW features a highly efficient (96%) economy mode setting that can significantly reduce a facility’s energy costs by minimizing heat output, reducing cooling requirements and consuming less electricity.

An LCD display with LED indicators enables IT personnel to operating modes and conditions. The LCD/LED panel rotates for viewing in horizontal rack or vertical tower installations and includes an audible alarm that signals various conditions.

The SU6000RT4UHVHW features a USB port and a DB9 ports for comprehensive network power monitoring and control. Network management card options available.

The unit requires only 4U of rack space in a standard rack enclosure and can be installed in a 2-post rack using the 2POSTRMKITHD accessory, or in a tower configuration with the 2-9USTAND accessory.

The SU6000RT4UHVHW comes with $250,000 Ultimate Lifetime Insurance (U.S., Canada, and Puerto Rico only) for connected equipment.

Features
Tripp Lite SU6000RT4UHVHW 6000VA / 6kVA / 5400 watt on-line, double-conversion UPS system in a single 4U rack/tower compatible housing
Full-time active power conditioning maintains clean, continuous dual-conversion AC output free of voltage fluctuations, power interruptions and line noise
Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions
Detachable back panel PDU contains hardwire input and output connections, plus manual bypass switch to support hot-swappable whole UPS replacement with no interruption to connected equipment
Hardwire input and output connections supported
Included rail kit supports 4U 19 inch rackmount installation in 4 post racks
Optional 2POSTRMKITHD supports installation in 2 post 19 inch racks (1 required for SU6000RT4UHVHW)
Optional 2-9USTAND supports upright tower placement (1 required for SU6000RT4UHVHW)
Maximum installed rack depth of only 20.7 in. / 52.6cm inches
Maintains full-time sine wave output within 2% of selected 200/208/220/230/240V nominal in double conversion mode
Corrects brownouts to 156V at full load (100V at 50% load or less)
Corrects overvoltages to 290V at full load (300V at 90% load or less)
Supports 50/60Hz operation for worldwide frequency compatibility
Double-conversion operation offers full-time AC to DC, then DC to AC conversion to maintain perfectly regulated sine wave AC output with enhanced protection from harmonic distortion, fast electrical impulses and other hard-to-solve power problems not addressed by other UPS types
High efficiency ECONOMY MODE operation significantly reduces BTU heat output and operating energy costs
Network-grade AC surge and noise suppression
Supports detailed monitoring of equipment load levels, self-test data and utility power conditions via built-in RS-232, USB and network management card options
Compatible with Tripp Lite UPS management card options TLNETCARD, WEBCARDLX, SNMPWEBCARD, MODBUSCARD and

RELAYIOCARD
Optional RELAYIOMINI interface module offers three configurable hard contact closure outputs for custom event notification (requires removal of USB interface module)
HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
USB & Serial ports enable data-saving unattended shutdown when used with Tripp Lite’s PowerAlert software, available via FREE download from www.tripplite.com/poweralert
Front panel LEDs and LCD readout with scroll controls support front-panel visual monitoring of all major
UPS functions with support for a variety of control options to support advanced UPS settings and configurations
LED/LCD display panel rotates for viewing in rackmount or tower configurations
Supports Emergency Power Off (EPO) via built-in interface
Battery independent restart ensures automatic UPS power-up without user interaction after lengthy power outages, even when batteries are expired and require replacement
BP192V12-3U external battery packs are field replaceable and hot swappable
Intelligent battery management system with temperature-compensated charging extends battery life
Some external battery configurations require the use of Tripp Lite’s External Battery Configuration Software (see manual)
Frequency conversion mode enables conversion of 60Hz to 50Hz or 50Hz to 60Hz (no de-rating)

Package Includes
SU6000RT4UHVPM Hot-swappable UPS Power Module
SUPDMB6KHW Detachable PDU with Maintenance Bypass Switch
1 x 6-ft. USB Cable
1 x 6-ft. DB9 Cable
4-Post Rackmount Hardware
Cisco compatible RoHS compliant VMware ready application

Specifications
UPC Code 037332157089
UPS Type On-Line

INPUT
Rated input current (Maximum Load) 31.9A (200V), 30.6A (208V), 29A (220V), 27.7A (230V), 26.6A (240V)
Nominal Input Voltage(s) Supported 200V AC; 208V AC; 220V AC; 230V AC; 240V AC
UPS Input Connection Type Hardwire
UPS Input Connection Description Supports North American 208/240V input (L1,L2,G) or International 230/220/240V (L,N,PE) input wiring
Recommended Electrical Service 40A (200/208v); 30A (220/230/240v)
Input Phase Single-Phase

OUTPUT
Output Volt Amp Capacity (VA) 6000
Output kVA Capacity (kVA) 6
Output Watt Capacity (Watts) 5400
Output kW Capacity (kW) 5.4
Output Capacity Details Supports up to 105% load continuously in double conversion mode, 106 to 125% for 1 minute, 126% to 150% for 30 seconds; Loads over 150% trigger immediate bypass mode operation to support loads directly from mains power; Double conversion mode is automatically restored as the overload is cleared
Power Factor 0,9
Crest Factor 3:1
Nominal Voltage Details Voltage selection via front panel LCD interface
Frequency Compatibility 50 / 60 Hz
Frequency Compatibility Details Output frequency matches input nominal on startup; Frequency conversion mode enables conversion of 60Hz to 50Hz or 50Hz to 60Hz (no de-rating)
Output Voltage Regulation (Line Mode) +/- 2%
Output Voltage Regulation (Economy Line Mode) +/- 10%
Output Voltage Regulation (Battery Mode) +/- 2%
Output Receptacle Details Hardwire input and output connections are mounted on a detachable PDU backplate with bypass switch to enable hot-swappable power module replacement
Output AC Waveform (AC Mode) Pure Sine wave
Output AC Waveform (Battery Mode) Pure Sine wave
Nominal Output Voltage(s) Supported 200V; 208V; 220V; 230V; 240V
Output Receptacles Hardwire
Individually Controllable Load Banks No

BATTERY
Battery Type Valve Regulated Lead Acid (VRLA)
Full Load Runtime (min.) 2 minutes (5400 watts)
Half Load Runtime (min.) 8.5 minutes (2700 watts)
Expandable Battery Runtime Runtime is expandable with external battery packs
Expandable Runtime Yes
External Battery Pack Compatibility BP192V1037C-1PH; BP192V12-3U ; BP192V1407C-1PH; BP192V557C-1PH; BP192V787C-1PH ; BP192V5RT2U (limit 1)
DC System Voltage (VDC) 192
Battery Recharge Rate (Included Batteries) 6 hours from 10% to 90% (typical, full load discharge)
Battery Access Front panel battery access door
Internal UPS Replacement Battery Cartridge RBC5-192
Battery Replacement Description Hot-swappable, user replaceable internal batteries

VOLTAGE REGULATION
Voltage Regulation Description Online, double-conversion power conditioning
Overvoltage Correction Corrects overvoltages as high as 300V (<90% load) and 280V (full load)
Undervoltage Correction Corrects undervoltages as low as 100 (<50% load) and 155V (full load); derates linearly

USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display Selectable LCD display with scroll and selection buttons enables UPS control and detailed monitoring options; LED/LCD panel rotates for viewing in rack/tower formats (see manual)
Switches Includes main power off/on switch, plus 2 switches to set and execute scrollable LCD functions. A manual bypass switch featured on the detachable PDU allows for complete removal of the UPS during routine maintenance without disrupting power to connected loads
Alarm Cancel Operation Alarm cancel switch
Audible Alarm Unique audible alarms for all major UPS, environmental and power conditions (see manual)
LED Indicators 6 LEDs indicate line power, online mode, economy/bypass mode, on-battery, charger and AC output status; LCD screen offers additional information and control options

SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating 2595
UPS AC Suppression Response Time Instantaneous
EMI / RFI AC Noise Suppression Yes

PHYSICAL
Cooling Method Fans
Included Mounting Accessory Description 4 post rackmount installation accessories included
Installation Form Factors Supported with Included Accessories 4 post 19 inch rackmount
Installation Form Factors Supported with Optional Accessories 2 post rackmount ( 2POSTRMKITHD ); Tower ( 2-9USTAND )
Maximum Device Depth (cm) 52.58
Maximum Device Depth (mm) 526
Minimum Required Rack Depth with External Battery Pack (cm) 74
Minimum Required Rack Depth with External Battery Pack (in.) 29
Minimum Required Rack Depth without External Battery Pack (cm) 53
Minimum Required Rack Depth without External Battery Pack (in.) 20.75
Primary Form Factor Rackmount
Primary UPS Depth (mm) 525
Primary UPS Height (mm) 174
Primary UPS Width (mm) 445
Rack Height 4U
Shipping Dimensions (hwd / cm) 32.26 x 59.94 x 73.91
Shipping Weight (kg) 70.99
UPS Housing Material Steel
UPS Power Module Dimensions (hwd, cm) 17.40 x 44.45 x 52.50
UPS Power Module Weight (kg) 52.71

ENVIRONMENTAL
Operating Temperature Range +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity 0 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load) 1767
AC Economy Mode BTU / Hr. (Full Load) 768
Battery Mode BTU / Hr. (Full Load) 2279
AC Mode Efficiency Rating (100% Load) 90%
AC Economy Mode Efficiency Rating (100% Load) 96%
Operating Elevation (ft.) 0-3000m (0 to 10,000 ft.)
Audible Noise 60 dBA at front side 1 meter
Operating Elevation (m) 0-3000 m

COMMUNICATIONS
Network Management Cards SNMPWEBCARD ; TLNETCARD ; WEBCARDLX ; MODBUSCARD ; RELAYIOCARD
Network Monitoring Port Description Additional contact closure support with optional RELAYIOCARD and RELAYIOMINI interface cards. RELAYIOMINI installation requires removal of panel containing USB ports
PowerAlert Software For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at http://www.tripplite.com/poweralert
Communications Cable USB, DB9 serial and EPO cables included
WatchDog Compatibility Yes
Communications Interface DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface; USB (HID enabled)

LINE / BATTERY TRANSFER
Transfer Time No transfer time (0 ms.) in online, double-conversion mode
Transfer Time (Economy Mode) 8 ms. typical power failure response in optional economy mode
Low Voltage Transfer to Battery Power (Setpoint) 156V (full load) / 100V (50% load or less, derates linearly)
High Voltage Transfer to Battery Power (Setpoint) 280V (full load) / 300V (90% load or less)

SPECIAL FEATURES
Cold Start (Startup in Battery Mode During a Power Failure) Cold-start operation supported
High Availability UPS Features Auto Probe Monitoring (requires WEBCARDLX); Automatic inverter bypass; Expandable battery backup; Hot swappable batteries; Hot swappable UPS power module; Manual bypass switch; On-Line/Double-Conversion; Remote management; Sine wave output; Zero transfer time
Green Energy-Saving Features High efficiency economy mode operation; Support for daily startup and shutoff; Schedulable daily hours of economy mode operation

STANDARDS & COMPLIANCE
UPS Certifications Tested to UL1778 (USA); Tested to CSA (Canada); CE; Meets FCC Part 15 Category A (EMI); ROHS (Restriction of Hazardous Substances)
Certification Details IEC 61000-4-5 1995 B Surge Immunity

WARRANTY
Product Warranty Period (Worldwide) 2-year limited warranty